燃气流量规定范围:2100(200-221m³/h),2800(266-294m³/h)。锅炉在出厂时参数已经设置完成。调试步骤:1,打开燃气管道阀门送气,激活低气压开关后,关闭燃气管道阀门。2,程序自动运行,屏幕会提示点火失败且无其他报警,说明程序运行正确。若屏幕出现其他故障代码,需根据故障代码表先处理故障。 若只报点火失败故障,则可以打开燃气,正常点火运行。3,点火运行后,调节功率。找到如图所示的界面。转速在900-6000之间调节。看燃气消耗量是否在规定流量范围内。若流量不够,需调节气阀。
0/5000
源语言: -
目标语言: -
结果 (英语) 1: [复制]
复制成功!
The specified range of gas flow: 2100 (200-221m³/h), 2800 (266-294m³/h). <br>The parameters of the boiler have been set before leaving the factory. <br>Debugging steps: <br>1. Open the gas pipeline valve to supply air, and after activating the low pressure switch, close the gas pipeline valve. <br>2. The program runs automatically, and the screen will prompt ignition failure and no other alarms, indicating that the program is running correctly. If other fault codes appear on the screen, the fault must be dealt with first according to the fault code table. If only the failure of ignition is reported, the gas can be turned on and the ignition will run normally. <br>3. After the ignition is running, adjust the power. Find the interface as shown in the figure. The speed is adjusted between 900-6000. See if the gas consumption is within the specified flow range. If the flow is not enough, the air valve needs to be adjusted.
正在翻译中..
结果 (英语) 2:[复制]
复制成功!
Gas flow range: 2100 (200-221m3/h), 2800 (266-294m3/h).<br>The parameters of the boiler have been set at the factory.<br>Commissioning steps:<br>1, open the gas pipeline valve gas supply, activate the low pressure switch, close the gas pipeline valve.<br>2, the program automatically runs, the screen will prompt the ignition failed and no other alarm, indicating that the program is running correctly. If there are other fault codes on the screen, the fault must be handled first according to the fault code table. If only the ignition failure is reported, the gas can be turned on and the ignition is running normally.<br>3, after ignition operation, adjust the power. Find the interface as shown. The speed is adjusted between 900-6000. See if the gas consumption is within the specified flow rate. If the flow is not enough, the air valve needs to be adjusted.
正在翻译中..
结果 (英语) 3:[复制]
复制成功!
The specified range of gas flow: 2100 (200-221m 3 / h), 2800 (266-294m 3 / h).<br>The parameters of the boiler have been set before delivery.<br>Debugging steps:<br>1. Open the gas pipeline valve for air supply, activate the low pressure switch, and then close the gas pipeline valve.<br>2. The program runs automatically, the screen will prompt ignition failure and no other alarm, indicating that the program runs correctly. If other fault codes appear on the screen, the fault should be handled according to the fault code table. If only the ignition failure fault is reported, the gas can be turned on and the normal ignition operation can be carried out.<br>3. Adjust the power after ignition operation. Find the interface shown in the figure. Adjust the speed between 6000 and 900. See whether the gas consumption is within the specified flow range. If the flow is not enough, adjust the valve.<br>
正在翻译中..
 
其它语言
本翻译工具支持: 世界语, 丹麦语, 乌克兰语, 乌兹别克语, 乌尔都语, 亚美尼亚语, 伊博语, 俄语, 保加利亚语, 信德语, 修纳语, 僧伽罗语, 克林贡语, 克罗地亚语, 冰岛语, 加利西亚语, 加泰罗尼亚语, 匈牙利语, 南非祖鲁语, 南非科萨语, 卡纳达语, 卢旺达语, 卢森堡语, 印地语, 印尼巽他语, 印尼爪哇语, 印尼语, 古吉拉特语, 吉尔吉斯语, 哈萨克语, 土库曼语, 土耳其语, 塔吉克语, 塞尔维亚语, 塞索托语, 夏威夷语, 奥利亚语, 威尔士语, 孟加拉语, 宿务语, 尼泊尔语, 巴斯克语, 布尔语(南非荷兰语), 希伯来语, 希腊语, 库尔德语, 弗里西语, 德语, 意大利语, 意第绪语, 拉丁语, 拉脱维亚语, 挪威语, 捷克语, 斯洛伐克语, 斯洛文尼亚语, 斯瓦希里语, 旁遮普语, 日语, 普什图语, 格鲁吉亚语, 毛利语, 法语, 波兰语, 波斯尼亚语, 波斯语, 泰卢固语, 泰米尔语, 泰语, 海地克里奥尔语, 爱尔兰语, 爱沙尼亚语, 瑞典语, 白俄罗斯语, 科西嘉语, 立陶宛语, 简体中文, 索马里语, 繁体中文, 约鲁巴语, 维吾尔语, 缅甸语, 罗马尼亚语, 老挝语, 自动识别, 芬兰语, 苏格兰盖尔语, 苗语, 英语, 荷兰语, 菲律宾语, 萨摩亚语, 葡萄牙语, 蒙古语, 西班牙语, 豪萨语, 越南语, 阿塞拜疆语, 阿姆哈拉语, 阿尔巴尼亚语, 阿拉伯语, 鞑靼语, 韩语, 马其顿语, 马尔加什语, 马拉地语, 马拉雅拉姆语, 马来语, 马耳他语, 高棉语, 齐切瓦语, 等语言的翻译.

Copyright ©2024 I Love Translation. All reserved.

E-mail: