Required value of insulation resistance: The requirements of isolated-phase enclosed bus manufacturers: insulation resistance is not less than 100MΩ; Requirement value of pouring busbar manufacturer: insulation resistance is not less than 1000MΩ; GB50150-2016 required value: insulation is not less than 300MΩ. So take the smallest standard as the basis.