High-voltage alarm<br>Fault phenomenon: After the compressor starts operation, its high pressure has been rising up to<br> To set the protection value of 2.0mpa jump, the fault light is on.<br>How to handle and check items: <br>1) Check the configuration and operation of the cooling water pump (reasonable selection in line with the unit flow)<br> pump of magnitude and head).<br>2) Check that the cooling pipe way filter is blocked (cleaning filter).<br>3) Check the temperature difference between the condenser in and out of the water, normal 3-5 degrees C (if the temperature is greater than<br> 5 degrees C, increase the flow).<br>4) Check that the fan is OK (the wind should be up).<br>5) Check the operation of the cooling tower, such as whether the belt is loose, fan and sprinkler<br> whether the belt is reversed (adjusts the tightness of the belt, changes the fan and sprinkler<br> direction of operation).