An ultra-low energy consumption demonstration building is taken as an example, and the data of ground source heat pump system operation in summer are combined to analyze the problems of large supply and return water temperature difference and small unit COP value of ground source heat pump system, and propose solutions;<br>According to the operation data, the cumulative cooling capacity during the test period is about 54650.8kw · h; in the early stage, the water temperature difference between the supply and return of the ground source heat pump is about 15oC, and the COP value of the unit is between 2.5 and 3.75. After the problem is solved, the water temperature difference between the supply and return is about 2 to 4oC, and the COP value of the unit is between 4.0 and 5.0.<br>Based on the operation test analysis, reference is provided to the reasonable operation of ground source heat pump in ultra-low energy consumption buildings.<br>[Key words] ultra low energy consumption building; ground source heat pump; energy consumption; COP value; problem analysis