Commissioning and operation analysis of ground source heat pump in summer<br>[Abstract] taking an ultra-low energy consumption demonstration building as an example, combined with the data of ground source heat pump system operation in summer, this paper analyzes the problems of large water temperature difference between the supply and return of ground source heat pump system and small COP value of the unit, and puts forward solutions; according to the operation data, the cumulative cooling capacity during the test period is about 54650.8kw · h; the water temperature difference between the supply and return of ground source heat pump in the early stage is 15 At about OC, the COP value of the unit is between 2.5 and 3.75, the temperature difference between the supply and return water is about 2 to 4 OC after the solution, and the COP value of the unit is between 4.0 and 5.0. Through the test and analysis of this operation, it can provide reference for the reasonable operation of ground source heat pump in ultra-low energy consumption buildings.<br>[Key words] ultra low energy consumption building; ground source heat pump; energy consumption; COP value; problem analysis