3.11.7.4 When inspecting and repairing the air door (using control equipment), <br>always fix the air door in the closed position and lock the air door mechanically. <br>3.11.7.5 The countermeasures in the event of a fire in the bag filter <br>immediately shut down the boiler. <br>Switch the dust collector to the bypass condition and reduce the flue gas flow. <br>Call the fire brigade. <br>Stop the operation of the ash conveying system. <br>After the fire is extinguished (after a few hours), take the following measures: <br>wear tights and wear a full mask. <br>Check whether the fan is running at the lowest speed. <br>Open all the doors and hatches of the building to ensure good ventilation on the top of the dust collector. <br>Carefully open the access door of the ash hopper to check the degree of fire hazard. <br>Check all filter bags and replace all damaged filter bags (see "Revision and Maintenance Section" in Part 2). <br>Check and clean the inside of the dust collector. <br>Start the dust collector.