1) The preparation, storage and distribution systems of purified water and water for injection are at risk of microbial growth.<br>1) "Cl-pol-203 process water" regulation:<br>The following aspects shall be considered in the design of water system,<br>The design of purified water and water for injection system must be based on the local drinking water situation, to ensure that the produced water can continue to meet the set quality standards, and prevent microbial breeding and pollution.<br>Purified water and deionized water can be prepared by reverse osmosis, distillation, ion exchange, ultrafiltration and other appropriate methods.<br>The water for injection shall be prepared by distillation method, and its design must ensure that the endotoxin can be removed and the subsequent generation of endotoxin can be prevented.<br>The respirator of the storage tank shall be a hydrophobic sterilizing filter that does not shed fiber and can be tested for integrity.<br>Good design of the project shall include loop circulation, dead angle control of the pipeline, smooth internal surface, proper material, proper flow rate control, complete emptying of the system, etc.<br>Return water temperature of water for injection > 70 ℃.<br>Conclusion: the existing SOP meets the requirements of the regulations.<br>
正在翻译中..