The inspection and testing of the carrier pressure switching device shall comply with the following regulations:<br>1 The insulation oil perforated voltage of the load tap switch shall comply with the provisions of Table 19.O.1 of this standard;<br>2 Under the transformer metavolt, the dynamic operation of the load-on split switch shall not be less than 2 cycles, and the electric operation shall not be less than one cycle, where the power supply voltage shall be 85% or more of the rated voltage when operating electricly. Operation should be cardless, connecting procedures, electrical and mechanical limits should be normal;